Smoke and CO alarms in rented homes: the rules
By Liam, OHMS GROUP LTD ·
Landlords in England must provide working smoke alarms and, where there is a fixed combustion appliance, carbon monoxide alarms. The legal minimum is set by the Smoke and Carbon Monoxide Alarm (England) Regulations 2015, as amended in 2022. The British Standard for home fire alarms, BS 5839-6, recommends a higher level of protection for rented homes, and many landlords and letting agents work to that.
What the law requires
Since 1 October 2022, landlords of most private and social rented homes in England must:
- Fit at least one smoke alarm on every storey that has a room used as living accommodation
- Fit a carbon monoxide alarm in any room used as living accommodation that contains a fixed combustion appliance, such as a gas boiler, gas fire or wood burner. Gas cookers are excluded
- Check that all required alarms are working on the day a new tenancy starts
- Repair or replace an alarm once told it is faulty
Local councils enforce the rules and can impose a penalty of up to £5,000 where a landlord fails to comply with a remedial notice. The regulations do not say whether alarms must be battery or mains powered.
What BS 5839-6 recommends
BS 5839-6 is the code of practice for fire detection and alarm systems in homes. It describes systems by grade, which is about the type of equipment and power supply, and category, which is about where alarms are fitted.
Grades
- Grade D1: mains powered alarms, each with a tamper-proof standby battery
- Grade D2: mains powered alarms, each with a standby battery the user can replace
- Grade F1 and F2: battery only alarms, with sealed or user-replaceable batteries
- Grades A and C: systems with a central control panel, used in larger homes and some HMOs
Categories
- LD3: escape routes, such as the hall and landing
- LD2: escape routes plus higher risk rooms, such as the kitchen and the main living room
- LD1: every room where a fire could start, apart from bathrooms and toilets
For rented homes, the 2019 edition of BS 5839-6 recommends at least a Grade D1, Category LD2 system: mains powered interlinked alarms with sealed standby batteries, a heat alarm in the kitchen and a smoke alarm in the main living room as well as the escape routes. Houses in multiple occupation can need more, and licensed HMOs often have specific fire safety conditions, so check with your council.
Why mains-wired interlinked alarms
Battery alarms meet the legal minimum, but batteries get removed or go flat. Mains powered alarms with sealed standby batteries carry on working if the power fails and do not depend on tenants changing batteries. Interlinked alarms all sound together, so a fire in the kitchen is heard in a bedroom upstairs with the door shut.
Fitting mains alarms usually means a short run of new cable and a connection to a lighting circuit or a dedicated circuit, which is straightforward to plan alongside an EICR or a consumer unit upgrade.
Where alarms go
Smoke and heat alarms are normally fitted on the ceiling, in the hall and on each landing, with extra alarms in the rooms the category calls for. Alarms are not fitted in bathrooms or shower rooms, and smoke alarms are kept away from kitchen doors where cooking fumes and steam cause false alarms. Carbon monoxide alarms go in the room with the appliance, positioned in line with the manufacturer's instructions.
Testing and records
BS 5839-6 recommends alarms are tested at least monthly using the test button. Show tenants how to do it and ask them to report faults. Keep a record of the start of tenancy check, signed by the tenant if possible, along with any repairs. Alarms carry a replacement date from the manufacturer, so note it and replace them in good time.
Other alarm types
Heat alarms are used in kitchens because cooking fumes cause false alarms with smoke alarms. Carbon monoxide alarms should meet BS EN 50291, and the government guidance on the regulations prefers sealed for life batteries where battery alarms are used.
Fire alarms for landlords in Medway and Maidstone
We install mains powered interlinked smoke, heat and carbon monoxide alarms to BS 5839-6, and larger systems for HMOs and blocks with communal areas. Our guide to fire alarm categories covers commercial and communal systems. See our fire alarm installation service, our landlord EICR service and our domestic electrical work. We cover Medway, Maidstone and the rest of Kent. Call 01622 278762.
Common questions
Do landlords have to fit mains-wired smoke alarms?
The regulations do not require mains alarms, but BS 5839-6 recommends mains powered interlinked alarms with sealed standby batteries for rented homes.
Is a CO alarm needed next to a gas cooker?
No. Gas cookers are excluded from the legal requirement. A CO alarm is required in rooms with other fixed combustion appliances, such as boilers and wood burners.
What is a Grade D1 LD2 system?
Mains powered interlinked alarms with tamper-proof standby batteries, covering escape routes plus the kitchen and main living room.