EICR codes C1, C2, C3 and FI explained

By Liam, OHMS GROUP LTD ·

An Electrical Installation Condition Report, or EICR, records the condition of the fixed wiring in a property. Anything the inspector finds wrong is listed as an observation and given a code: C1, C2, C3 or FI. Those codes decide whether the report is satisfactory or unsatisfactory, and they tell you how urgently each item needs attention.

If you have just been handed a report with a page of codes on it, this guide explains what they mean in plain English.

What an EICR actually looks at

The inspection covers the fixed installation: the consumer unit, the circuits leaving it, earthing and bonding, and the condition of sockets, switches and fittings. The electrician inspects visually and carries out tests with the power off and on, then records the results circuit by circuit. Plug-in appliances are not part of an EICR. They are covered separately by portable appliance testing where that is needed.

Most EICRs are carried out on a sample basis agreed at the start. A good report states the extent of the inspection and any limitations, such as rooms that could not be accessed or cables hidden behind fitted units.

C1: danger present

C1 means there is a risk of injury right now and immediate action is needed. Typical examples are exposed live parts that can be touched, such as a broken socket front or a missing blanking plate in the consumer unit.

An electrician who finds a C1 should tell the person responsible straight away and, with their agreement, make it safe before leaving, either by repairing it or by isolating the affected part. A C1 makes the whole report unsatisfactory.

C2: potentially dangerous

C2 means the fault is not dangerous at this moment but could become so if something else goes wrong, for example a fault on an appliance. Common C2 items include:

  • Missing or inadequate main protective bonding to gas or water pipes
  • No RCD protection on socket outlets that could be used to supply equipment outdoors
  • Earth continuity problems found during testing
  • Signs of overheating at connections or accessories

C2 items should be put right urgently. One C2 is enough to make the report unsatisfactory.

C3: improvement recommended

C3 is advisory. The installation does not meet the current edition of BS 7671 in some respect, but it is not considered unsafe. Older consumer units without RCD protection on every circuit are often coded C3 where nothing else points to a danger. C3 items on their own do not make a report unsatisfactory, but they are worth planning for, especially if you are already having other work done.

FI: further investigation required

FI means the inspector found something that needs looking into but could not get to the bottom of it during the inspection. A circuit that could not be traced or a test result that does not make sense would be typical. An FI makes the report unsatisfactory until the investigation is done, because nobody yet knows whether a danger is hiding behind it.

Satisfactory or unsatisfactory

The overall outcome follows a simple rule. Any C1, C2 or FI means the report is unsatisfactory. If there are only C3 items, or none at all, the report is satisfactory.

An unsatisfactory report does not mean the house has to be rewired. In most cases it means a short list of specific faults to correct. Once they are done, the electrician issues paperwork confirming the remedial work, and for landlords that confirmation matters as much as the report itself.

What to do with your report

  1. Read the summary and the outcome first, then each coded observation.
  2. Ask the inspector to explain any item you do not understand. A good report describes the problem and where it is, not just a regulation number.
  3. Get a written quote for the C1, C2 and FI items. You do not have to use the same company that wrote the report.
  4. Keep the report and the remedial certificates together. You will want both for insurers, tenants, buyers or the council.

If you are a landlord, the timescales for remedial work are set in law. We cover those in a separate guide on landlord electrical safety.

EICRs in Maidstone, Aylesford and across Kent

We carry out domestic and commercial EICRs with plain English reports, and we quote for any remedial work separately so you are never pressured into repairs on the spot. See our electrical testing and EICR service, or if your report points to an old board, our consumer unit and rewiring service. We are based in Aylesford and cover Maidstone and the surrounding area. Call 01622 278762 to book an inspection.

Common questions

Does a C3 make an EICR unsatisfactory?

No. C3 is a recommendation for improvement. Only C1, C2 or FI observations make a report unsatisfactory.

Is an old fuse box automatically a fail?

Not automatically. It is coded on its condition and the protection it gives. Missing RCD protection is often C3, but other faults found with it can make it C2.

Do I have to use the same electrician for the repairs?

No. You can get quotes from any competent electrician. Ask for written confirmation once the work is complete.